   Natural Gas Fired Generator

    

Click for a Larger Image

SOLAR TAURUS 60

3697 HOURS 

230 STARTS

5.2 MW

13,800 VOLTS

3 PHASE, 60 HZ.

TRAILER MOUNT

 

 Generator nameplate rating per NEMA standards is 6,625 Kva at 0.8 power factor (5,300kw) 13,800 volts at 104°F (40°C), 3281 ft (1000 m) elevation for continuous duty. The generator is rated so that the generator will not limit turbine performance over the range of site ambient temperatures.

  

 

 

 

· Voltage Regulator Characteristics

· Solid state

· Single-phase sensing

· ±10% voltage adjustment range

· 0.5% steady state voltage regulation

· Reactive load sharing to within 5% nameplate rating

· Crosscurrent compensation capability

· Wave Form Characteristics

  

· Generator Standard Features

· Sleeve Bearings with pressure fed sumps

· Six-lead WYE connection

· Terminal box

· Form wound stator windings

· Damper windings

· Rotor balance to 125% rated speed

· Permanent magnet pilot exciter

· Anti-condensation space heaters

· 300% short circuit capability for 10 seconds

Overload capacity per NEMA:

· 150% rated current for 1 minute (b) 110% for 2 hours

Deviation Factor [maximum]

Harmonic Content [maximum]

Telephone Interference Factor

Balanced Residual

 

Voltage Drift. The change in voltage will not exceed 1.0% over a 30-minute period when the generator is operating at rated voltage and 0.8 to 1.0 power factor and with a constant load between no load and full rated load.

Generator Voltage. The generator output is 13,800 Volt, 3 phase, 60 Hz.    

Insulation conforms to NEMA class F.

 