1149 Ellsworth
|
|
Natural Gas Fired GeneratorSOLAR TAURUS 60 3697 HOURS 230 STARTS 5.2 MW 13,800 VOLTS 3 PHASE, 60 HZ. TRAILER MOUNT
· Voltage Regulator Characteristics · Solid state · Single-phase sensing · ±10% voltage adjustment range · 0.5% steady state voltage regulation · Reactive load sharing to within 5% nameplate rating · Crosscurrent compensation capability · Wave Form Characteristics · Generator Standard Features · Sleeve Bearings with pressure fed sumps · Six-lead WYE connection · Terminal box · Form wound stator windings · Damper windings · Rotor balance to 125% rated speed · Permanent magnet pilot exciter · Anti-condensation space heaters · 300% short circuit capability for 10 seconds Overload capacity per NEMA:
· 150% rated current for 1 minute (b) 110% for 2 hours
Voltage Drift. The change in voltage will not exceed 1.0% over a 30-minute period when the generator is operating at rated voltage and 0.8 to 1.0 power factor and with a constant load between no load and full rated load. Generator Voltage. The generator output is 13,800 Volt, 3 phase, 60 Hz. Insulation conforms to NEMA class F.
|
|